MX350 Controller
The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.
Rating Range | Switch Dependent |
---|---|
Transfer Type | Application Dependent |
Switch Type | Application Dependent |
Communications Interface - Optional | Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) |
---|---|
Control Power | 120 VAC |
Load Control Relay Contacts (1) | rated for 10A @ 24VDC or 120VAC |
Load Control Relay Contacts (2) | 0-259 minutes |
Overfrequency Dropout for Source 1 and Source 2 | 50.1 - 63 Hz |
Overfrequency Restore for Source 1 and Source 2 | 50 - 62.9 Hz |
Overvoltage Dropout for Source 1 and Source 2 | 105 - 110% of nominal |
Overvoltage Restore for Source 1 and Source 2 | 103 - 108% of nominal |
Source Sensing | 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) |
Voltage Unbalance for Restore for Source 1 and Source 2 | 4 to 19% of nominal |
Voltage Unbalance on Dropout for Source 1 and Source 2 | 5 to 20% of nominal |
Undervoltage Dropout for Source 1 and Source 2 | 75-99% of nominal |
Undervoltage Restore for Source 1 and Source 2 | 85-100% of nominal |
Underfrequency Dropout for Source 1 and Source 2 | 45 - 59.9 Hz |
Underfrequency Restore for Source 1 and Source 2 | 45 - 59.5 Hz |
Delay for Engine Cool Down (U) | 0-60 minutes |
Delay Transfer to Nonpreferred Source (W) | 0-5 minutes |
Delay NeutralTransition Time Delays (DT,DW) | 0-10 minutes |
Storage Temperature | (-40˚C - 90˚C ) |
Operating Temperature Ambient | (-20˚C to 50˚C) |