C32 ACERT generator sets incorporate a separate circuit aftercooling system (SCAC) for all configurations. The primary advantage of the SCAC systsem is reduced aftercooler corrosion since no sea water circulates through the aftercooler. Many other improvements on these engines contribute to minimizing owning and operating costs. The EPA Tier 3, IMO II, EU Stage IIIA compliant ratings are available with heat exchanger or keel cooled options. Heat exchanger configurations have an optional front mounted sea water pump.
Aspiration
Turbocharged and aftercooled
Bore
145 mm
Displacement
32.1 l
Engine Model
Vee-12, 4-stroke-Cycle-Diesel
Fuel System
MEUI
Governor Type
Electronic
Stroke
162 mm
Emissions/Fuel Strategy
EPA Tier III
Frequency
60hz
Maximum Rating
940 ekW (1175 kVA)
Minimum Rating
730 ekW (913 kVA)
Speed
1800 rpm
Excitation
Permanent magnet
Number of Poles
4
Number of Bearings
2 roller bearings
Number of Leads
6
Insulation
Class H
IP Rating
23
Voltage Regulator
CDVR
Width
1528 mm
Height
1667 mm
Weight - Estimated
7131 kg
Length
162.8 in/4271 mm (minimum), 175.3 in/4452 mm (maximum)